LMU1 Line Monitoring Unit 1 way

Order code LMU1

Line monitoring Unit for supervision of 1 speaker circuit.

Product Description

The LMU1 Line monitoring unit is used when monitoring of a single speaker circuit is required. In the event of an open speaker circuit, a yellow led will indicate the zone affected and activate the fault relay. If a short on speaker circuit is detected the LMU4 will isolate that zone only, a red led will indicate zone affected and activate the fault relay. A green led indicates normal conditions. Switching of each zone is possible by placing the PTT link to the top position (factory set in LOCK) and place 0V on the PTT or A/C  terminal input to activate, this is often used for P.A zone switching. Supplied with plug in terminals.
LMU1 is compatible with Evactron SD and SZ series OWS can be used on most amplifier outputs directly from 100v transformers.
For multiple circuit applications, LMU4 cards are available.

SPECIFICATIONS
Voltage supply 23-30vdc
Max load per card- 100 watts
Voltage output- up to 100 volt line
Current draw 90mA
Fuse Self resetting
Fault contacts N.O contact closes in a fault condition. N.C opens in a fault condition.
Indication- yellow for open circuit and red for short, common green led for normal condition.
Monitor Output – 0V for S/C, +24V with O/C condition (usedEV2000 series using Keypad Fascia)
PTT – Optional zone switching, 0v to activate (P.T.T factory set to LOCK)
End Of Line Resistor 22k at end of each speaker zone.
Dimensions 75L x 85W x 22mmH

 

LMU1pdficon_large